INDUSTRIAL MODULAR DC UPS

INDUSTRIAL MODULAR DC UPS

STRUCTURE:

- input AC distribution with measurement, protections and distribution (supply rectifiers),

  type: IZBN 1f (3f) – xx                                                                                                                                        

- rectifiers / battery chargers, 1 to 24 pcs in parallel, „n+1“ principle, with fan or natural cooling                         

  type: MPL,  MPLP (high power UPS) or  PFC, KMB, ESP, PBR (UPS low power UPS)                                

- battery, Lead-acid or Ni-Cd, 1 or 2 sets

- battery protection (over current, deep discharge, short circuit)

- measuring unit (currents, voltages, temperatures)

  type: MJ

- microprocessor unit for local and remote monitoring and control

  type: MPJ 02 (03) or MPJ 04

- DC / DC converters (if there needs to be multiple different DC voltage outputs)

  type: IDC, ZDC, LLC, SIP

- output DC distribution with protections (MCCB, MCB, fuses), one or more output voltages, with or without selective disconnection

- cabinet, one or more (rectifiers cabinet + battery cabinet + DC/DC cabinet + voltage distribution cabinet + DC connecting cabinet)

INPUT:

- 230 V, 50 / 60 Hz

- 3 x 400 / 230 V, 50 / 60 Hz 

OUTPUT:

one or more output voltages

- 24 VDC, 

- 48 VDC, 

- 60 VDC,

- 110 VDC,

- 125 VDC, 

- 220 VDC

POWER:

100 W to 100 kW

AUTONOMY:

To 100  hours

LEVELS OF DISTRIBUTION SELECTIVITY:

1 to 4

UPS TYPE (order code):

- one output voltage

  IBN xxx – yyy – zzz  (xxx – nominal output voltage,  yyy – output current,  zzz – capacity of battery C10)

  For example, IBN 110 – 80 – 200  P (or without P), with P – naturally cooled rectifiers, without P – fan-cooled  rectifiers

  Values: 110 VDC output voltage,  80 A output current, battery C10 = 200 Ah)

- two or more output voltages

  For example: IBN 110/120 – 48/50 – 350
  Output 1:  110 VDC – 120 A  (rectifiers 110 VDC – 120 A), fan cooled rectifiers

  Output 2:    48 VDC – 50 A  (DC / DC converters 110 VDC / 48 VDC – 50 A)

  Battery C10 = 350 Ah, the battery is charged with 110 VDC

- the customer needs to define the number, technology and nominal values of the output switches (MCCB, MCB, fuse)